§ 10-52306.2.3. ABOVE-GROUND TANKS LOCATED OUTSIDE OF BUILDINGS, ABOVE GRADE.  


Latest version.
  • 1.

    Above-ground tanks used for outside above grade storage of Class I and II liquids shall be listed and labeled as protected above-ground tanks in accordance with Chapter 57. Such tanks shall be located in accordance with Table 2306.2.3.

    2.

    Above-ground tanks used for above grade storage of Class III-A liquids are allowed to be protected above-ground tanks, or when approved by the fire code official, other above-ground tanks that comply with Chapter 57. Tank locations shall be in accordance with Table 2306.2.3.

    3.

    Tanks containing fuels shall not exceed 12,000 gallons (45 420 L) in individual capacity or 48,000 gallons (181 680 L) in aggregate capacity. Installations with the maximum allowable aggregate capacity shall be separated from other such installations by not less than 100 feet (30 480 mm).

    4.

    Tanks located at farms, construction projects, or rural areas shall comply with Section 5706.2 (et. al.).